Technical specification

Generator specifications.

Diesel generating sets, 20 kVA and above, 50 Hz, three phase. The figures below are typical for each size and are confirmed for your unit in writing on your quotation.

How to read this page

Frame data is typical for the size shown and is confirmed unit by unit in your quotation. Sizes between those shown follow the same design and are quoted on request.

Range we supply

We supply from 20 kVA upward. Detailed data for 35 to 200 kVA and for 250 to 800 kVA is below. Larger sets are quoted on request, with the frame, the freight and the lead time fixed in writing.

Frame data

Dimensions, weights and fuel figures are typical for the frame size shown.

Ratings and output

Rating35 kVA100 kVA200 kVA
Standby power(kVA)35100200
Standby power(kW)28.280160
Prime power(kVA)31.990.9180
Prime power(kW)24.772.7145
Engine speed(rpm)150015001500
Rated voltage(V)400 / 230400 / 230400 / 230
Frequency(Hz)505050
Power factor0.80.80.8

Engine and fuel

Rating35 kVA100 kVA200 kVA
Cylinders4 in line4 in line6 in line
Displacement(L)3.64.67.6
Bore x stroke(mm)100 x 115105 x 135110 x 135
Compression ratio17:117:117:1
AspirationNaturalTurbocharged, intercooledTurbocharged, intercooled
CoolingLiquidLiquidLiquid
InjectionDirectDirectDirect
Fuel at 100 percent load(l/h)9.223.440.2
Fuel at 75 percent load(l/h)6.917.530.1
Fuel at 50 percent load(l/h)4.611.720.1
Starting battery12 V / 60 A24 V / 2 x 60 A24 V / 2 x 60 A

Dimensions and weight

Rating35 kVA100 kVA200 kVA
Canopied L x W x H(mm)2000 x 950 x 14402400 x 1000 x 16402800 x 1100 x 1830
Canopied dry weight(kg)99413631816
Open set L x W x H(mm)2000 x 950 x 11002400 x 1000 x 13002800 x 1100 x 1490
Open set dry weight(kg)74110881436
Fuel tank(L)120170250

Larger sets, 250 to 800 kVA

Prime rated, silent canopied sets. Dimensions and weight are approximate for the canopied set with base fuel tank and are confirmed on your quotation.

Ratings and output

Rating250 kVA400 kVA500 kVA650 kVA800 kVA
Prime power(kVA)250400500650800
Prime power(kW)200320400520640
Engine speed(rpm)15001500150015001500
Rated voltage(V)400 / 230400 / 230400 / 230400 / 230400 / 230
Frequency(Hz)5050505050
Cylinders6 in line6 in line6 in line6 in line6 in line
AspirationTurbocharged, intercooledTurbocharged, intercooledTurbocharged, intercooledTurbocharged, intercooledTurbocharged, intercooled
Canopied L x W x H(mm)3700 x 1500 x 21004200 x 1800 x 25004500 x 1800 x 25004800 x 2000 x 26005800 x 2300 x 2600
Canopied weight, approx.(kg)36504200480066009800

Alternator and build

These hold across our sets from 20 to 200 kVA. For larger sets the alternator data is stated on your quotation.

Type
Brushless, three phase, synchronous, self exciting
Poles
4
Connection
Three phase four wire, star
Insulation class
H
Enclosure protection
IP23
Voltage regulation
AVR, plus or minus 1 percent steady state
Total harmonic distortion
3 percent or less
Overload
110 percent for 1 hour in every 12, prime rating
Windings
Copper

Options confirmed per order

Frequency and voltage

Other voltages and 60 Hz on request. State the standard in your enquiry and it is confirmed in writing before the order is placed.

Control panel

Automatic control with an LCD display as standard. The panel model is named in your quotation.

ATS

Automatic transfer switch available on request, always stated as a line item on your quote.

Alternator upgrade

A premium alternator is available as a paid upgrade where local parts availability and resale value matter. It is quoted as a separate line, never substituted silently.

Canopy and finish

Sound attenuated steel canopy with exhaust silencer. Up to 200 kVA, emergency stop, control window and electrostatic powder coating are standard. Colour and branding confirmed per order.

Fuel tank

Base frame tank sized as shown.

Sound level

The sound level for your unit is written into your quotation before the order is placed.

Testing and documents

Every set is tested before dispatch. The test report, the independent inspection report, the operation manual and the conformity documents your market requires ship with the goods, and every one of them is listed on your quotation.

Need a size that is not on this page?

Send the rating, the voltage and frequency standard where it is going, and whether you need prime or standby. We come back with the exact specification and a written quotation.

Request a specification→